RG16R16 0,6/1 kV Repero®

CPR (UE) n°305/11 Construction Products Regulation
Cca – s3, d1, a3 Class according to standards EN 50575:2014 + A1:2016 and EN 13501-6:2014
CEI 20-13 – CEI UNEL 35376 Construction & Specifications
CEI EN 60332-1-2 Flame propagation
2014/35/UE Low Voltage Directive
2011/65/CE RoHS Directive

Product Info

Product Description

Description

High-quality G16 insulated ethylene-propylene rubber cables, PVC sheath, with special fire reaction characteristics and according to Construction Products Regulation (CPR).

Conductor
Plain copper stranded wire, class 2

Insulation
Rubber HEPR compound, G7 quality

Filler
Non-hygroscopic compound

Outer Sheath
PVC compound, R16 quality

Cores Colour
HD 308 Standard

Sheath Colour
Grey

Inkjet Marking
BALDASSARI CAVI REPERO® RG16R16 0,6/1 kV (section)
Cca-s3,d1,a3 (year) (m) (traceability)

Technical Characteristics

Nominal voltage Uo/U: 0,6/1 kV

Maximum operating temperature: 90°C
Minimum operating temperature: -15°C
(without mechanical stress)
Minimum installation temperature: 0°C

Maximum short-circuit temperature: 250°C up to 240 mm² section, over 220°C
Maximum tensile stress: 50 N/mm2
Minimum bending radius: 6 x maximum external diameter

Use and Installation

Cables suitable for the electrical power system in constructions and other civil engineering works in order to limit fire spread and smoke emission. Power cables for industrial and/or residential uses. Suitable to be used indoor and outdoor, even in wet environments; it can be fixed on walls and/or metal structures. Suitable also for laying underground. (ref. CEI 20-67)